General Information : Pressure Relief Valve is a safety element of the transformer employs to prevent heavy damages of the tank in the case of sudden rise of the internal pressure. These Valve have been designed in order to remove the excess pressure in a very short time as soon as the pressure in the tank rises above predetermined safe limit the valve operates and allow the pressure to drip instantaneously, it avoids damage to transformer body.
Operating : The PRVs port is sealed with viton O ring and sealing cap, kept sealed by stainless steel rod & stainless steel spring. The sealing cap is exposed to tank pressure, whenever same pressure rises due to any reason, the same pressure acts on the sealing cap from inside. When pressure rises above predetermined safe limit, the sealing cap gets lifted from its seat. This lifting is instantaneous and allows vapors, gases or liquid to come out of tank. The sealing cap regains its position as soon as pressure in the tank drop below the set limit. S-3 & S-16
is provided with weather proof IP 67 limit switch with lever, visible
mechanical indicator & rain guard. The visible indicator shows Normal
(Green) / Abnormal (red) condition of transformer. The switch & visible
indicator is actuated by movement of sealing cap and switch to be reset
manually, it automatically resets visible indicator. All PRV is provided
with splash guard and drain plug to prevent oil to splash all over the
transformer, and a safe passage to splashed oil when PRV operates
Main Characteristics
|
Model: T-10 |
Model : S-3 |
Model : S-16 |
|
(For distribution transformers) |
(For power transformers) |
|
Material:
- Brass
forged body & brass sealing cap
- Sealing
rubber (Viton)
-
Hardened Steel spring
|
- Alu.
Diecast body, Splash guard & SS sealing cap
- Sealing
rubber (Viton)
-
Hardened steel spring
|
|
Specification :
v 1 BSP |
v 65 mm |
v 150 mm |
- Op.
Pressure : 0.30, 0.42, 0.49, 0.56, 0.70, kg/cm2 any one value as per
order
|
- Op.
Tolerance : + 0.05kg/cm2
|
- Op.
Time : Instantaneously
|
|
Available on request |
- Contact
Rating : AC415V 1.5 Amps DC230V 0.1 Amps
- No. of
Contact : 1No/1Nc[4 terminal]
|
|
Valve : Automatic
Switch : --
Indicator : -- |
Automatic
Manual
Automatic |
Automatic
Manual
Manual |
|
50 x 50 x 75 mm |
150 x 150
x 200 mm |
250 x 260
x 250 mm |
Routine Test :
All PRVs are checked for leakage test by compressed air with required
pressure and sealed before dispatched, test certificate accompany
consignment.
Installation :
Tank cover or side to be provided with necessary tapped hole for mounting of
PRV Vertically / horizontally as per mounting detail.
|